IM-P343-29 CH Issue 5 31
9.2.3 RETRN - RTAIN - RESET
Programming notes
Provides the facility to restore previous permanently stored values (RETRN),
to retain values stored in the temporary memory (
RTAIN) or to reset all values
to factory default settings (
RESET). Press and keys to select RETRN,
RTAIN or RESET. To advance proceed as follows:
RETRN
To cancel any temporary changes to programmed values select
RETRN and
press key to return to SP200 MENU.
RTAIN
To retain temporary changes to programmed values select RTAIN and
press key to return to SP200 MENU.
RESET
Provides the facility to reset all values to factory default settings and return to
SET UP NOW. Press and hold
key for 3 seconds. The display will count down
the 3 seconds.
Commissioning notes
RETRN
If changes have been made to program values they will be held in the temporary memory.
To retain changes in the permanent memory it is necessary to advance to RUN in the main
menu and press and hold key for 3 seconds. The display will count down the 3 seconds.
If you do not wish to retain temporary changes select
RETRN and press key to return
to SP200 MENU.
RTAIN
If changes have been made to programmed values they will be held in the temporary memory.
If you wish to retain these changes select
RTAIN and press key to return to SP200 MENU.
To retain temporary changes in the permanent memory advance to
RUN in the main
menu and press and hold
key for 3 seconds. The display will count down the 3 seconds.
RESET
Resetting to default values (refer to Section 9 for default values) should be used if it is intended
to use the positioner on a different control valve. If the SP200 positioner has been moved
on its mounting or is to be fitted on a different control valve it will be necessary to undertake
a new autostroke (AUTOS).
RESET to factory default settings can also be used if it is required to recommission the valve.
To reset to factory default values
select RESET and press and hold key for 3 seconds.
The display will count down the 3 seconds.